Air Compressor Performance Testing
in Vapi
Gujarat

Flow · Leak Rate · ISO 8573 Air Quality · Energy Audit · Vapi · Silvassa · Daman · Surat

Performance Testing
Measured. Documented. Certified.
Written Test Certificate for Audit Use
+91 90999 72929

Know exactly what your compressed air system is delivering. Pressure, flow, leak rate, ISO 8573 air quality and energy consumption — measured, documented and certified. Vapi · Silvassa · Daman · Surat.

  • Flow & pressure testing
  • ISO 8573 air quality classification
  • Leak detection
  • Written test certificate
What Gets Measured

On Every Test

  • Actual flow rate vs rated capacity (CFM / m³/min)
  • Discharge pressure at full load vs rated bar
  • Air leak rate — % of total output lost to leaks
  • ISO 8573 air quality — oil, particles, moisture
  • Energy consumption — kWh per m³ of air produced
  • Specific Power — efficiency benchmark vs nameplate
Why Testing Is Neglected

3 Things Your Factory Believes About Its Compressed Air System That Are Probably Wrong

Most factories in Vapi GIDC assume their compressed air system is performing correctly because production is running. That assumption is almost always wrong.

01

"Running" and "Performing" Are Not the Same

A compressor rated at 300 CFM might be delivering only 220 CFM — a 27% shortfall — with no alarm ever triggering. A performance test takes 2–3 hours and tells you exactly where your system stands. The shortfall is almost never the compressor itself.

02

Air Leaks Are Stealing 20–40% of Your Bill

20–40% of all compressed air generated typically never reaches any productive use — lost through leaks that are inaudible in a running factory. Factories that fix high-priority leaks after a test typically cut their electricity bill by 15–25%.

03

The Certificate Is on the Wall, the Air Was Never Tested

Documentation may still say Class 0 while the air at the point of use has drifted to Class 3 or worse. A performance test measures actual air quality and produces current, live audit evidence.

Comprehensive System Audit

What Our Performance Test Measures

Calibrated instruments, objective measurements at multiple points in your system.

Compressor Output — Flow Rate

Actual free air delivery (FAD) measured in m³/min or CFM against manufacturer rated capacity. Volumetric efficiency also calculated for reciprocating units.

System Pressure Drop

Pressure measured at discharge and multiple downstream points. A correctly designed system should have less than 0.3 bar total drop from compressor to user.

System Leak Test

Pressure decay measured during shutdown to calculate total leak rate as a % of output, plus ultrasonic detection to locate and prioritise individual leak points.

ISO 8573 Air Quality

Oil content down to 0.01 mg/m³, particle count and size, and pressure dewpoint measured and classified against the ISO 8573 scale.

Energy Audit — Specific Power

Electricity consumption (kWh) measured against air output (m³) and compared to the manufacturer's rated Specific Power for your model.

Temperature Profile

Readings at inlet, interstage, discharge and oil temperature — early warning signs of problems caught before they become a breakdown.

Leak Loss

How Much Is Your Factory Losing to Air Leaks?

A typical industrial system in Vapi loses 20–40% of its output through leaks — most inaudible during production. For a factory running a 100 HP compressor:

20

% Leak — Well-Maintained System

35

% Leak — Average Vapi Factory

40

%+ Leak — Poorly Maintained

Based on a 100 HP compressor, ₹8/kWh, 20 hr/day, 300 working days/year.

ISO 8573 Air Quality

ISO 8573 Air Quality Classes — What They Mean for Your Industry

The international standard classifying compressed air purity. We test and certify against these classes.

ISO 8573 Class Oil Content (mg/m³) Particles (0.1–0.5 µm) Pressure Dewpoint Who Needs It
Class 0 As specified (essentially zero) As specified As specified Pharma (WHO GMP), food direct contact, electronics
Class 1 0.01 mg/m³ ≤ 20,000/m³ −70°C Pharma instrument air, high-purity food
Class 2 0.1 mg/m³ ≤ 400,000/m³ −40°C Paint booths, sensitive instruments, food packaging
Class 3 1 mg/m³ ≤ 90 million/m³ −20°C General industrial processes
Class 4 5 mg/m³ ≤ 10 million/m³ +3°C Pneumatic tools, general workshop use

If your industry requires Class 0 or Class 1 and your air has never been tested since installation, call +91 90999 72929. A single test takes 2–3 hours and produces a certificate valid for regulatory audits.

Who Needs a Performance Test

6 Situations Where a Performance Test Is Needed Immediately

Pharma Plant Before GMP Audit

Drug inspectors increasingly ask for compressed air quality certificates, not just equipment documentation.

Electricity Bill Increased Unexplained

Almost always a leak rate issue or compressor efficiency degradation.

Machines Not Getting Enough Pressure

A test identifies whether the issue is compressor output or distribution system pressure drop.

Food Plant Before FSSAI Audit

FSSAI auditors require evidence that compressed air in contact with food is oil-free and clean.

Before Adding a New Compressor

Often reveals existing capacity being wasted to leaks — fixing them may remove the need for a second unit entirely.

Annual Energy Audit Requirement

Plants under BEE or ISO 50001 energy management need documented energy performance data.

Test Certificate

What You Receive After the Performance Test

  • Actual flow rate (FAD) vs rated capacity in m³/min or CFM
  • Pressure readings at discharge, receiver, header and point-of-use
  • Pressure drop across each section of the distribution system
  • System leak rate as a percentage of total compressor output
  • Prioritised leak repair list (high, medium, low priority)
  • ISO 8573 air quality classification for oil, particles and moisture
  • Specific Power (kWh/m³) vs manufacturer specification
  • Temperature profile at all key measurement points
  • Corrective action recommendations with priority ranking
  • Test certificate signed by RR Enterprise engineer — valid for audits
FAQs

Frequently Asked Questions — Compressed Air Performance Testing in Vapi

Questions from maintenance engineers, plant managers and purchase heads in Vapi GIDC, Silvassa and Daman.

Performance testing is a systematic measurement of your compressed air system's actual output, efficiency, leak rate, air quality and energy consumption using calibrated instruments. Any factory in Vapi where the compressor has not been tested since installation, where the electricity bill has increased, where downstream machines aren't getting enough pressure, or where a GMP/FSSAI audit is approaching should commission a test. It takes 2–3 hours on site and produces a written certificate.

A comprehensive performance test measures: actual flow rate (FAD) versus rated capacity, system pressure drop from compressor to point of use, total system leak rate, ISO 8573 air quality (oil content, particle count, pressure dewpoint), specific power consumption (kWh per m³), and temperature profile at key points. Results are presented in a written certificate with corrective action recommendations.
Industrial compressed air systems in Indian factories typically lose 20–40% of total output through leaks. For a factory running a 100 HP compressor at ₹8/kWh for 20 hours per day, a 35% leak rate wastes approximately ₹2–2.5 lakh per year in electricity alone. Most leaks are inaudible during production and are detected only during a formal leak test.
Yes. RR Enterprise provides ISO 8573 compressed air quality testing at pharmaceutical, food and other compliance-sensitive plants in Vapi, Silvassa, Daman and Surat. We measure oil content, particle count and pressure dewpoint at the point of use and issue a formal ISO 8573 classification certificate, accepted as audit evidence by GMP and FSSAI auditors. Call +91 90999 72929 to book.
For pharma and food manufacturers with GMP/FSSAI requirements, an ISO 8573 test should be done annually — or after any major maintenance event. For general industrial plants, a performance test every 2–3 years is recommended, or whenever electricity consumption increases without explanation. Leak testing should be done annually as part of energy management.
Yes, consistently. Leak repair typically reduces compressor electricity consumption by 15–25%. And if the system is running at a higher pressure than needed — common when pressure is raised to compensate for undersized piping — reducing the set pressure saves roughly 7% in compressor electricity consumption per 1 bar reduction.
The report includes: actual FAD versus rated capacity, full pressure profile from compressor to point of use, system leak rate in CFM/m³/min and as a percentage of output, prioritised leak repair list, ISO 8573 air quality classification certificate, specific power consumption versus rated value, temperature profile, and a corrective action plan prioritised by financial impact. Signed by our engineer and presentable to auditors and management.
Our Clients

Trusted by Gujarat’s Leading Industries

Sun Pharma, Emami, Sumul, Supreme Group, Megafine, Faze Three and more.

Book a Compressed Air Performance Test in Vapi

Flow · Leak Rate · ISO 8573 · Energy Audit · Written Certificate
Vapi · Silvassa · Daman · Surat

×

Get a Free Quote